| Technical
Data and Specifications |
| Reference standards |
UL 810 / IEC 60252-1 / EIA 456 A Jan.89 |
| Safety class to IEC 60252-1 2001-02 |
P2 |
| Life expectancy to IEC 60252 2001 |
250 - 450V: 10,000h (Class B) |
| Life expectancy to EIA 456 A Jan. 89 |
60,000 hours at 95% survival rate |
| Rated capacitance CR |
3 - 50µF |
| Tolerance |
±5% other tolerances on request |
| Rated voltage VR |
250 / 370 / 400 / 450VAC |
| Rated frequency fR |
50/60 Hz |
| Maximum Ratings |
| Maximum permissible voltage Vmax |
1.1 · VR (VR = Rated voltage) |
| Maximum permissible current Imax |
1.3 · IR (IR = Rated current) |
| Test Data |
| AC test voltage terminal to terminal VTT |
2.0 VR, 10 s |
| Insulation voltage terminals to case |
3000 V AC, 2 s |
| Insulation resistance Rins or time constant at 20 ⁰C, rel. Humidity ≤ 65% (minimum as-delivered values) |
10,000 MΩ µF |
| Dissipation factor at 20 ⁰C |
≤2.0 10-3 (100 Hz) |
| Maximum rate of voltage rise dV/dtmax |
10 V/µs |
| Climatic Data |
| Climatic category |
40/070/21 |
| Lower category Tmin |
-40⁰C |
| Upper category Tmax |
+70⁰C |
| Damp heat test ttest |
21 days |
| Mechanical and
Thermal Properties of Insulation Terminal Material |
| Ball pressure test to IEC 60309-1 sec.
27.3 |
20 N at 125⁰C |
| UL 94 specification |
V0 compatible |
| Glow wire test to IEC60335-1 / IEC
60695-2-1/1 Test temperature 550 ⁰C for IR ≤0.5A
and 750 ⁰C for IR >0.5A |
Self-extinguishing within 2 seconds of withdrawing glow wire |